Request a quote
Duct Hi-Limit Humidistat

Use

Prevents over-humidification in ducts by shutting off the humidifier when RH exceeds the set limit.

Specifications

  • Control Mode: ON/OFF
  • Set Point Range: 15–95% RH
  • Accuracy: ±1.5% RH
  • Contacts: SPDT (NO & NC), 5A @ 24Vac/Vdc
  • Switching Differential: 4% RH

High Efficiency Steam Distribution

Request a quote
Duct Air Proving Switch

Use

Ensures humidifier operates only when airflow is present in the duct.

Specifications

  • Control Mode: ON/OFF
  • Set Point Range: 0.08–1.2 in w.c. (20–300 Pa)
  • Max Pressure: 30 in w.c. (7500 Pa)
  • Contacts: SPDT (NO & NC), 2A @ 250Vac or 1A @ 30Vdc
  • Max Switching Frequency: 6 cycles/min

SB - Space blower

Request a quote
Floor Leak Switch

Use

Detects water accumulation on the floor to prevent water damage.

  • Supply Voltage: 11–27 Vac/Vdc
  • Relay: SPDT, 1A @ 24Vac/Vdc
  • Indicators: Green LED = Power On, Red LED = Alarm
  • Probe: Gold-plated, adjustable
  • Housing: Cast aluminum with stainless steel cover

Other Isothermal Humidifiers Products

IER Electric Steam Humidifier

Produces steam on demand for commercial, institutional or industrial applications.

IER Electric Steam Humidifier

RES Residential Steam Humidifier

Produces pure steam on demand for safe home humidity.

RES Residential Steam Humidifier

ISE Steam Exchange

Generates clean steam using a heat exchanger circulating raw pressurized steam or High temperature hot water.

ISE Steam Exchange

ILS Live Steam Humidifier

Uses pressurized steam from a steam boiler as a direct source of humidity for air duct or AHU.

ILS Live Steam Humidifier